《保护层分析-LayersOfProtAnaly.ppt》由会员分享,可在线阅读,更多相关《保护层分析-LayersOfProtAnaly.ppt(22页珍藏版)》请在得力文库 - 分享文档赚钱的网站上搜索。
1、 ABB-Page 1E x t e n d e d A u t o m a t i o n S y s t e m 8 0 0 x AFunctional safety Engineering-Layers of Protection ABB -Page 2FunctionalsafetyLayers of Protection AnalysisnFault Propagation ContextnEvent Tree MethodnLayers of Protection DefinitionnLOPA Event TreenInitiating Evnents and Failure R
2、atesnExample of Layers of Protection ABB -Page 3FunctionalsafetyFault Propagation modellingnAnalyze the Chain of events that leads to an accident Control SystemFailsOperator does not respond properlyMechanical relief failedOverpressure EventInitiating event ABB -Page 4FunctionalsafetyLayers of Prote
3、ction Analysis-LOPAnA variant of Event Tree AnalysisnMore structuresnLike event tree analysis,the initiating event start the chain of eventsnBranches are layers of protectionnConsider only two outcomenAccidentnNo Event ABB -Page 5FunctionalsafetyLOPA Version of Event TreePL2,failsPL1,failsPL3,failsA
4、ccidentQuantify using multiplications;all logical ANDs ABB -Page 6FunctionalsafetyEx,Column Rupture LOPAnDraw the LOPA diagram for following situationsnConsequence of the accident=fire due to distillation column rupture has a root cause of loss of cooling waternLayers of protectionnOperator respond
5、to alarms and stops the processnProcess generally designed to withstand loss of cooling waternThe column has a pressure relief valvenSource of ignition are controlled in the process area ABB -Page 7FunctionalsafetyEx:Column rupture LOPA ABB -Page 8FunctionalsafetyLOPA CalculationsnProceed as with ev
6、ent tree,but only need to calculate the frequency of accidentnResulting accident frequency is initiating event frequency multiplied by PFD of all protection layersnExamplenCooling water failure frequency is 0,5/yearnProtection layersnOperator response failure PFD=0,15nRelief valve failure PFD =0,07n
7、Process design inadequate PFD=0,01nIgnition source contacted PFD=0,3 ABB -Page 9FunctionalsafetyEx:Column Rupture,LOPAF=0,5/y*0,15*0,01*0,07*0,3=1,58E-5 per year ABB -Page 10FunctionalsafetyFailure Rate QuantificationnHistorical reliability data specific to your installation is best,but often diffic
8、ult to getnPlant maintenance and SIS function test data by equipment typenIndustry average data grouped by equipment typenSome expert judgment is still inevitable ABB -Page 11FunctionalsafetyUsing Maintenance and Function Test DatanCompanies usually keep maintenance logsnIEC 61511 requires function
9、testing and documentation of resultsnFunction test data used to approximate failure rate:nSimple Equation for point estimate of failure rate:=#Failures/Total Unit of Operation=Failure rate ABB -Page 12FunctionalsafetyPFD from Failure RatenPFD depends on failure rate,failure mode and test intervalnFa
10、ilure rate is divided into failures that can cause a false trip versus those that failure on demandnMost databases list the failure mode for an equipment itemnAn untested devices PFD gets larger as the operational time interval increasesnFor devices subject to periodic inspection and test the averag
11、e PDF can be usedPDFavg (t)/2 ABB -Page 13FunctionalsafetyTypical Protection LayersnBPCSnThe BPCS and SIS are physically separated devices,including sensors,logic solvers and final elementsnFailure of the BPCS is not responsible for initiating the unwanted accidentnBPCS has the proper sensor and act
12、uators available to perform a function similar to the one performed by the SIS PDF 0,1(By definition)ABB -Page 14FunctionalsafetyTypical Protection LayersnOperator ResponsenOperator always Present nOperator has indication of ProblemnOperator has time to ActnOperator is Trained in the Proper Response
13、PDF 0,1,if all condition is metPDF=1,0,if condition not met ABB -Page 15FunctionalsafetyTypical Protection LayersnUse factor(Time at Risk)nHazard is not always presentnEx Batch production ABB -Page 16FunctionalsafetyTypical Protection LayersnMechanical Integrity of VesselnIs vessel designed to withs
14、tand the pressure and temperature generated as a result of the initiating event?nMechanical Relied DevicesnRelief ValvesnRupture DisknFusible PlugsnPFD calculated based on failure rate statistics found in database ABB -Page 17FunctionalsafetyTypical Protection LayersnExternal Risk ReductionnWater Sp
15、ray CurtainsnDual Walled pipingnEnclosures with ScrubingnOnly consider LOPA if protection system will COMPLETELY ELIMINATE the CONSEQUENCE ABB -Page 18FunctionalsafetyTypical Protection LayersnIgnition ProbabilitynMost plants are designed to limit sources of IgnitionnFunction of release size and rel
16、eased materialnP 0,3 for flammable gasesnP 0,1-0,3 for volatile gasesnP 0,1 for heavy liquid ABB -Page 21FunctionalsafetyLayers of Protection AnalysisnFault Propagation ContextnEvent Tree MethodnLayers of Prote tion DefinitionnLOPA Event TreenInitiating Evnents and Failure RatesnExample of Layers of Protection ABB -Page 22Functionalsafety